1. Due to population expansion and economic development, the phenomenon of water shortage is appearing successively in many parts of the world, especially in cities. Although China's hydropower resources can be developed up to 379 million kilowatts, but per capita less than 0.3 kilowatts. "China's Water Saving technology Policy Outline" points out: "Vigorously develop and promote industrial water reuse technology, improve the reuse rate of water is the primary way of industrial water saving, the development of efficient cooling water saving technology is the focus of industrial water saving." Condensation cooling equipment is a large industrial energy consumption of water, cooling energy consumption accounted for 13% to 15% of industrial energy, water consumption accounted for 70% to 80% of industrial water, and indirect cooling water accounted for 70% to 80% of cooling water. It is also in this case that evaporative condensation technology came into being and has become one of the important technologies for water recycling and reuse. Evaporative condensation technology plays an important role in aviation, electric power, machinery, textile and other industrial fields. At the same time, cooling tower, spray tower, evaporative condenser, etc. are the key equipment for the reuse of cooling water, and the energy-saving and water-saving effect of evaporative condenser is not only obvious in theory, but also has been well proved in practical application. Therefore, the research and development of evaporative condensing cooling equipment is of great practical significance.
2 Evaporative condenser
According to the working principle of evaporative condenser, because evaporative condenser mainly uses the latent heat of vaporization of water to take away the condensing heat released during the condensation process of refrigerant, the amount of cooling water is much less than that of water-cooled condenser. The actual amount of water added is 1/25-1/50 of the water-cooled type, which is especially suitable for water-scarce areas.
The performance and water consumption of various condensers are compared respectively. It is calculated that when ammonia is used as refrigerant and the cooling capacity is 3·8×106kJ/h, the evaporative condenser saves 3·4×105kWh of electricity per year on average than the shell and tube condenser.