Air cooler common failure forms and solutions

In the use of air cooler, failure is the most common problem encountered by user friends. According to the communication and interaction with customers in the after-sales service, the common failure forms and solutions are sorted out and shared with you as a maintenance reference.

 

1 Blade damage: the main reason is improper blade installation and blade material defects

Blade is the key component of air cooling, and its running state is related to the effect of air cooling. The blades of an air cooler in a unit were broken, and DCS showed that the fan was stopped by overcurrent. After the equipment and maintenance arrived at the scene, it was found that the fan blades were seriously damaged, and the fan inlet filter was cut open about 1 meter. Fortunately, the response was timely and there were no casualties and the production of the device was not affected.

 

The main reason for the fan failure is that the blade clamp and connecting bolt of the crosshead are broken, causing the fan blade to fall off and hit other blades and the filter screen. The failure is a material problem, in the application of air cooler, many enterprises in order to save costs for the selection of its component material is not enough attention, ignoring the fan in the high-speed rotation of the component friction and other factors caused by the damage, the blade shaft quality is not up to standard, it is easy to cause fracture, coupled with high maintenance difficulty, the production operation has a great impact.

 

Treatment measures: blade material upgrade, bearing seat improvement, reduce the vibration of the fan, scientific installation.

 

2 Heat exchange tube and tube bundle leak

The main reasons are corrosion, material defects and long service life of the tube bundle

Treatment measures: chemical glue or punch card glue on common leakage points; Serious need to replace the tube bundle and heat exchange tube

 

3 Poor effect of air cooler

The main reason is the inner wall of the fin tube fouling, bending blockage and fin deformation

Treatment measures: Purge or clean the air cooler, and check and repair the damaged fins

 

4 The fan system is faulty

Common fan system faults mainly include: ammeter indication abnormal, low gas flow, abnormal vibration of transmission components, abnormal sound and high temperature of rotating components

Treatment measures: recalibrate the balanced installation, check the tightness of the belt, tighten the bolts, replace the bearing and add or replace the grease regularly, and strictly abide by the management regulations of the dynamic equipment.

In production practice, failure problems require correct operation and regular maintenance to maximize prevention. We can prevent and maintain the common faults of the air cooler in advance to reduce the impact of air cooling faults on the normal operation of the device. At the same time, it can also improve the use effect of the air cooler and promote the optimal operation of the device.