The evaporative condenser is composed of a cooling tube group, water supply equipment, fan, water baffle, box, etc. The cooling tube group is a serpentine coil group made of seamless steel pipe bent and installed in a rectangular box made of thin steel plate. The two sides or top of the box are provided with a fan, and the bottom of the box is also used as a cooling water circulation pool.
The working principle of the evaporative condenser is to send high-temperature steam that needs to be condensed from the upper inlet of the heat exchange coil into the coil tube, and the high-temperature steam emits heat in the heat exchange coil tube and becomes a liquid after cooling. The circulating spray water is used as the cooling medium outside the heat exchange coil, and the spray water forms a uniform water film on the outer surface of the heat exchange coil. The water film absorbs the heat released by the hot steam inside the coil and evaporates, and then the water steam is taken out of the evaporating condenser by the fan.
1) The nozzle is blocked, causing the condensing tube group to be not uniformly wetted, so that the condensing pressure rises, and it needs to be cleaned frequently.
2) Pipe group scaling: equipped with an advanced electronic water scaling meter, in addition, it can also control the accumulation of impurities by controlling the cycle of circulating water and sewage.
3) The reasonable distribution of water.
4) Corrosion problem.
5) The wet bulb temperature ts1 of the imported air is related to the local meteorological conditions.
6) Air volume is related to ts1. The higher the ts1, the greater the required air supply volume, and the more energy consumption. Therefore, the supply air volume should be equipped with two aspects of energy saving and performance requirements.
7) The water quantity is equipped to ensure the wetting of all heat exchange surfaces. Increasing the water distribution at will will cause the pump power consumption to rise, the water dissipation loss to increase, and the operating cost to increase.